ALM-10774 No AC Input Alarm

Description

This alarm is reported when the DHEU has no AC input.

Attribute

Alarm ID Alarm Severity Alarm Type
10774 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

74:DHEU

95:DTCU

3 Board No.

Number of the fault board

0:DHEU/DTCU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

15:BTS3012AE;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The heater cannot work normally when the alarm is generated.

System Actions

None.

Possible Causes

  • The BTS has no AC power supply.
  • The AC distribution switch of the heat exchanger is not switched on.
  • The AC socket of the heat exchanger is not properly connected.
  • The transformer of the heat exchanger is faulty.

Procedure

  1. Check whether the AC distribution switch of the DHEU is switched on.

    Y=> Go to step 3.

    N=> Go to step 2.

  2. Switch on the AC distribution switch of the DHEU.

    Observe whether the alarm is cleared after the AC distribution switch is switched on.

    Y=> The alarm is cleared. Alarm handling is complete.

    N=> The alarm is not cleared. Go to step 3.

  3. Check whether the AC socket of the DHEU is properly connected.

    Y=> Go to step 5.

    N=> Go to step 4.

  4. Reconnect the AC socket of the DHEU.

    Observe whether the alarm is cleared after the reconnection.

    Y=> The alarm is cleared. Alarm handling is complete.

    N=> The alarm is not cleared. Go to step 5.

  5. Replace the transformer of the DHEU.

    Observe whether the alarm is cleared after the replacement.

    Y=>The alarm is cleared. Alarm handling is complete.

    N=> The alarm is not cleared.Please contact Huawei Customer Service Center.


Huawei Proprietary and Confidential