ALM-10776 Compressor of air-condition Alarm

Description

This alarm is reported when the compressor of the air-conditioner is abnormal.

Attribute

Alarm ID Alarm Severity Alarm Type
10776 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

74:DHEU

95:DTCU

3 Board No.

Number of the fault board

0:DHEU/DTCU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

0:No current in the compressor

1:High voltage in the compressor

2:Frequent high voltage in the compressor

3:Low voltage in the compressor

4:Frequent low voltage in the compressor

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

15:BTS3012AE;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The heat dissipation of the system is affected.

System Actions

None.

Possible Causes

  • Compressor current alarm
  • The air switch that controls the compressor is disconnected or the cable that connected to the compressor is improperly plugged.
  • Low voltage alarm or frequent low voltage alarm
  • The internal circulation air inlet or outlet is blocked.
  • High voltage alarm or frequent high voltage alarm
  • The external circulation air inlet or outlet is blocked.

Procedure

  1. Compressor current alarm

    Check whether the air switch is abnormally disconnected or the cable that connected to the compressor is improperly plugged.

  2. High voltage alarm or frequent high voltage alarm

    Check whether the external circulation air inlet or outlet is blocked or whether the condenser is blocked.

  3. Low voltage alarm or frequent low voltage alarm

    Check whether the internal circulation air inlet or outlet is block.

    Adhere to the preceding steps and rectify the fault accordingly. Check whether the alarm is cleared.

    Y=> The alarm is cleared. The alarm handling is complete.

    N=> The alarm persists. Please contact Huawei Customer Service Center.