ALM-10782 Filter Alarm

Description

This alarm is reported when the resistance of the filter increases due to the accumulation of dust.

Attribute

Alarm ID Alarm Severity Alarm Type
10782 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

74:DHEU

95:DTCU

3 Board No.

Number of the fault board

0:DHEU/DTCU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

0:Dust filter alarm (warning)

1:Dust filter alarm (critical)

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

15:BTS3012AE;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

  • The dust filter alarm affects the heat dissipation in the BTS.
  • The first phase alarm (warning) : the operator should to clean the dust filter or replace the dust filter. The heat dissipation of the system deteriorates.
  • The second phase alarm (critical) : the operator should to replace the dust filter immediately. The heat dissipation mechanism of the system breaks down.

System Actions

None.

Possible Causes

The long operation of the heat exchanger leads to the accumulation of dust on the dust filter. The service life of the dust filter expires as its resistance increases. Thus, the dust filter should be replaced.

Procedure

  1. The first phase alarm (warning): Check whether the dust filter is Clean, if not,clean it.

  2. The second phase alarm (critical): Replace the dust filter .

  3. Check whether the alarm is cleared.

    Y=> The alarm is cleared. The alarm handling is complete.

    N=> The alarm persists.Please contact Huawei Customer Service Center.


Huawei Proprietary and Confidential