ALM-10794 Door Alarm

Description

This alarm is reported when the cabinet door is opened without permission or when the door status sensor is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type
10794 Critical Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

95:DTCU

3 Board No.

Number of the fault board

0:USCU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

20:DBS3036;

21:BTS3036;

22:BTS3036A;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The burglarproof function of the cabinet is adversely affected.

System Actions

None.

Possible Causes

  • The cabinet door is opened without permission.
  • The door status sensor is faulty.

Procedure

  1. Check the status of the cabinet door.
    1. Check whether the cabinet door is opened.

      Y => The cabinet door is opened. Check the equipment for damage or displacement in the equipment room. Take proper measures to restore the equipment if necessary.

      N => The cabinet door is not opened. Go to procedure 2.

  2. Check the door status sensor and cable connections related to the door status sensor.
    1. Check whether the door status sensor is faulty or the related cable connections are improper.

      Y => The door status sensor is faulty, the related cable connections are improper, or the door status sensor is installed incorrectly. Go to procedure 3.

      N => None of the above faults exists. Contact Huawei.

  3. Replace the faulty door status sensor, reinstall the related cables, or reinstall the door status sensor.
    1. Check whether the door alarm is cleared.

      Y => The alarm is cleared. No further action is required.

      N => The alarm is not cleared. Contact Huawei.