ID | Name | Meaning |
---|---|---|
1 | Site No. | Number of the site where the faulty board or module is located Value range: 0-2047 |
2 | Board Type | Number of the type which the faulty board belongs to. 162:GMU |
3 | Board No. | Number of the fault board 0:GMU |
4 | PassNo | Number of the passage where the faulty board is located. |
5 | SubLink No. | Alarm sub-category number 255:None |
6 | Cell Index | Index of the cell where the board or module is located 0-2047: Cell index of the faulty cell in the data configuration 65535: None |
7 | Site Type | Type of the site where the faulty board is located. 30:BTS3900E; |
8 | RackNo | Number of the rack where the faulty board is located. |
9 | BoxNo | Number of the subrack where the faulty board is located. |
10 | SlotNo | Number of the slot where the faulty board is located. |
11 | Site Name | Site Name |
12 | Alarm Attribute | Alarm Character 0:Normal 1:Transient Count |
When this alarm is generated, the surge protection module in the surge protection device is damaged. This lowers the surge protection capability of the BTS. The BTS, if struck by lightening again, may be damaged.
Y => The DC surge protector is faulty. Go to step b.
N => The DC surge protector is functional. Go to procedure 2.
Y => The alarm is cleared. No further action is required.
N => The alarm is not cleared. Go to procedure 2.
Y => The alarm is cleared. No further action is required.
N => The alarm is not cleared. Contact Huawei Customer Service Center.