ALM-13088 Ambient Temperature Abnormal

Description

This alarm is reported when the ambient temperature is too high or too low.

Attribute

Alarm ID Alarm Severity Alarm Type
13088 Minor Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

162:GMU

3 Board No.

Number of the fault board

0:GMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

1: Too high

2: Too low

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

30:BTS3900E;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

13 Problem 1: Too high 2: Too low

Problem

1: Too high

2: Too low

Impact on the System

The equipment is prone to damage because of overtemperature.

System Actions

None.

Possible Causes

  • The air-conditioner or the heat exchanger does not work properly, which leads to overtemperature or undertemperature in the equipment room.
  • The temperature and humidity sensors are faulty and report the false alarm.
  • The alarm threshold is set improperly.
  • The EMU is faulty.

Procedure

  1. Check the threshold of the ambient temperature alarm.
    1. Check the ambient temperature alarm threshold and determine whether the high and low temperature alarm thresholds are set properly.

      Y => The thresholds are properly set. Go to procedure 2.

      N => The threshold are improperly set. Go to step b.

    2. Change the ambient temperature alarm threshold. Check whether the alarm is cleared.

      Y => The alarm is cleared. No further action is required.

      N => The alarm is not cleared. Go to procedure 2.

  2. Check the air conditioner or heat exchanger.
    1. Check whether the air conditioner or the heat exchanger is functional.

      Y => The air conditioner or the heat exchanger is functional. Go to procedure 3.

      N => The air conditioner or heat exchanger is faulty. Rectify the fault.

  3. Replace the EMU, and then check whether the alarm is cleared.

    Y => The alarm is cleared. No further action is required.

    N => The alarm is not cleared. Contact Huawei Customer Service Center.