ALM-13092 Cabinet Temperature Abnormal

Description

The cabinet temperature is too high or too low.

Attribute

Alarm ID Alarm Severity Alarm Type
13092 Minor Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

162:GMU

3 Board No.

Number of the fault board

0:GMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

1: Too high

2: Too low

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

30:BTS3900E;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

13 Problem 1: Too high 2: Too low

Problem

1: Too high

2: Too low

Impact on the System

If the cabinet temperature is too high, the TRX starts overtemperature protection. Thus, the ongoing services are disrupted.

System Actions

None.

Possible Causes

  • The cabinet temperature is too high or too low.
  • The temperature sensor is faulty.

Procedure

  1. Check the cabinet temperature.

    How to check the temperature threshold: Run the LST BTSEXD command on the MML client and set the parameters as required(IDTYPE=BYID, BTSID=BTS Index).

    Y => The cabinet temperature is higher than the temperature upper threshold. Go to procedure 2.

    N => The cabinet temperature is normal. Contact Huawei Customer Service Center.

  2. Check the state of the air conditioner and fan.

    If the air conditioner or fan is faulty, rectify the fault. Wait until the cabinet temperature is normal, and then check whether the alarm is cleared.

    Y => The alarm is cleared. No further action is required.

    N => The alarm is not cleared. Go to procedure 3.

  3. Check the preset threshold.

    Check whether the preset threshold is too low. The normal cabinet temperature ranges from 0 to 40 degrees Celsius.

    Y => The preset threshold is too low. Modify the threshold.

    Log in to the LMT. Right-click the target site, and then choose Site Operation > Configure Site Attributes. Click Extended Attributes in the displayed Configure Site Attributes dialog box. Then, modify the temperature upper threshold. After the modification is complete, check whether the alarm is cleared. If the alarm is cleared, no further action is required. If the alarm is not cleared, go to procedure [4].

    N => The preset threshold is in the normal range. Go to procedure 4.

  4. Check the temperature sensor.

    Check the state of the temperature sensor. Replace the temperature sensor if it is faulty. Then, check whether the alarm is cleared.

    Y => The alarm is cleared. No further action is required.

    N => The alarm is not cleared. Contact Huawei Customer Service Center.