ID | Name | Meaning |
---|---|---|
1 | Site No. | Number of the site where the faulty board or module is located Value range: 0-2047 |
2 | Board Type | Number of the type which the faulty board belongs to. 162:GMU |
3 | Board No. | Number of the fault board 0:GMU |
4 | PassNo | Number of the passage where the faulty board is located. |
5 | SubLink No. | Alarm sub-category number 1: Too high 2: Too low |
6 | Cell Index | Index of the cell where the board or module is located 0-2047: Cell index of the faulty cell in the data configuration 65535: None |
7 | Site Type | Type of the site where the faulty board is located. 30:BTS3900E; |
8 | RackNo | Number of the rack where the faulty board is located. |
9 | BoxNo | Number of the subrack where the faulty board is located. |
10 | SlotNo | Number of the slot where the faulty board is located. |
11 | Site Name | Site Name |
12 | Alarm Attribute | Alarm Character 0:Normal 1:Transient Count |
13 | Problem 1: Too high 2: Too low | Problem 1: Too high 2: Too low |
The fans rotate at their full speed and thus generate uncomfortable noise. The intelligent temperature control fails.
Y => The temperature reported is the same as the actual temperature. Go to procedure 2.
N => The temperature reported is different from the actual temperature. Go to procedure 4.
Y => The temperature is normal. No further action is required.
N => Go to procedure 3.
Y => The alarm is cleared. No further action is required.
N => The alarm is not cleared. Go to procedure 4.
Y => The alarm is cleared. No further action is required.
N => The alarm is not cleared. Contact Huawei Customer Service Center.