ALM-2330 DC Lowvoltage Alarm

Description

This alarm is triggered when the DC output is lower than the threshold.

Attribute

Alarm ID Alarm Severity Alarm Type
2330 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

85:PMU

3 Board No.

Number of the fault board

0:PMU 0

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board or module is located

3: BTS30

5: BTS312

10: BTS3012A

11: BTS3006A

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The services supported by the BTS may be interrupted due to power supply failure.

System Actions

None.

Possible Causes

  • The DC output is lower than 22.5V (when the number of power modules is not 0) or lower than 19V (when the number of power modules is 0).
  • The power module fails or is overloaded.

Procedure

  1. Check the power module

    Replace the power modules one by one and measure the output voltage of the busbar to see whether there are any power modules faulty. Replace the faulty power module if any and then measure whether the output voltage of the busbar is higher than the threshold.

    Y=> The alarm handling ends if the alarm is cleared after the replacement. If otherwise,Please contact Huawei Customer Service Center.

    N=>Go to Step 2.

  2. Add new power module as per load requirement.

    Add new power modules and measure whether the output voltage of the busbar is higher than the threshold.

    Y=> The alarm handling ends if the alarm is cleared after the addition of new power modules.If otherwise, Please contact Huawei Customer Service Center.

    N=> Please contact Huawei Customer Service Center.