ALM-2342 Rack Low Humidity Alarm

Description

This alarm is reported when the cabinet humidity is below the lower limit.

Attribute

Alarm ID Alarm Severity Alarm Type
2342 Minor Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

85:PMU

3 Board No.

Number of the fault board

0:TMU0

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

3: BTS30

5: BTS312

10: BTS3012A

11: BTS3006A

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The services may be affected by over-low humidity.

System Actions

None.

Possible Causes

  • The cabinet humidity is below 10%RH (RH is the relative humidity).
  • The humidity sensor is damaged.

Procedure

  1. Measure the cabinet humidity.

    Check whether the measured humidity is below the lower limit.

    Y=>Go to Step 2.

    N=>The humidity is normal. Go to Step 3.

  2. Increase the humidity.

    Check whether the alarm is cleared.

    Y=>The alarm is cleared. Alarm handling is complete.

    N=>The alarm is not cleared. Go to Step 3.

  3. Replace the humidity sensor.

    Check whether the alarm is cleared.

    Y=>The alarm is cleared. Alarm handling is complete.

    N=>The alarm is not cleared. Please contact Huawei Customer Service Center.