ALM-2378 Low Temperature Alarm

Description

This alarm is triggered when the environment temperature is lower than the lower temperature threshold.

Attribute

Alarm ID Alarm Severity Alarm Type
2378 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

13:EAC

3 Board No.

Number of the fault board

0:Number of EAC

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board or module is located

3: BTS30

5: BTS312

11: BTS3006A

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

Services may be interrupted since the environment temperature is too low.

System Actions

None.

Possible Causes

  • The environment temperature is lower than the lower temperature threshold.
  • The setting of the lower temperature threshold is unreasonable.
  • The temperature sensor or the cable connecting to the temperature sensor is faulty.
  • The board in the environment alarm box fails.

Procedure

  1. Check whether the lower temperature threshold set for the environment alarm box is too high.

    Query the lower temperature threshold set for the environment alarm box on the LMT to see whether the setting is too high.

    Y=>Set a reasonable value for the lower temperature threshold. View whether the alarm is cleared. The alarm handling ends if the alarm is cleared, and go to Step [2] if otherwise.

    N=>Go to Step 2.

  2. Check whether the temperature in the equipment room is too low

    The normal temperature for BTS30 and BTS312 to work is between -5 °C and 45 °C. Check whether the temperature in the equipment room is lower than the threshold.

    Y=>Start the warming air conditioner.

    N=> Go to Step 3.

  3. Check the temperature sensor and the cable connecting to the temperature sensor.

    Replace the temperature sensor or the connection cable if faulty. View whether the alarm is cleared.

    Y=> The alarm handling ends.

    N=> Go to Step 4.

  4. Check whether the board in the alarm box is faulty

    Replace the board in the alarm box. View whether the alarm is cleared.

    Y=> The alarm handling ends.

    N=> Please contact Huawei Customer Service Center.