ALM-2382 Low Humidity Alarm

Description

This alarm is triggered when the environment humidity is too low.

Attribute

Alarm ID Alarm Severity Alarm Type
2382 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

13:EAC

3 Board No.

Number of the fault board

0:Number of EAC

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board or module is located

3: BTS30

5: BTS312

11: BTS3006A

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

Services may be interrupted when the environment humidity is too low.

System Actions

None.

Possible Causes

  • The environment humidity is lower than the lower humidity threshold.
  • The setting of the lower humidity threshold is unreasonable.
  • The humidity sensor or the cable connecting to the humidity sensor is faulty.
  • The board in the environment alarm box fails.

Procedure

  1. Check the lower humidity threshold set for the environment alarm box.

    Check whether the lower humidity threshold set for the environment alarm box is too high.

    Y=> Set a reasonable value for the lower humidity threshold. View whether the alarm is cleared. The alarm handling ends if the alarm is cleared, and go to Step [2] if otherwise.

    N=> Go to Step 2.

  2. Check the humidity in the equipment room

    Check whether the humidity in the equipment room is lower than the lower humidity threshold. The normal humidity for BTS to work is between 15%RH and 85%RH.

    Y=>Raise the humidity in the equipment room. View whether the alarm is cleared after the humidity is proper. The alarm handling ends if the alarm is cleared, and go to Step [3] if otherwise.

    N=> Go to Step 3.

  3. Check the humidity sensor and the cable connecting to the humidity sensor.

    Replace the humidity sensor or the connection cable if faulty. View whether the alarm is cleared.

    Y=> The alarm handling ends.

    N=> Go to Step 4.

  4. Check whether the board in the alarm box is faulty

    Replace the board in the alarm box. View whether the alarm is cleared.

    Y=> The alarm handling ends.

    N=> Please contact Huawei Customer Service Center.