ALM-2504 Voltage Regulator Alarm

Description

This alarm is triggered when BTS3012A voltage regulator works abnormally or the AC power supply fails.

Attribute

Alarm ID Alarm Severity Alarm Type
2504 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

140:OSSU

3 Board No.

Number of the fault board

0:OSSU0

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board or module is located

10: BTS3012A

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

If the alarm is caused by output failure of the voltage regulator, the air-conditioner stops running for BTS3012A air-conditioner cabinet, so does the heat exchanger for BTS3012A heat exchanger cabinet.

System Actions

None.

Possible Causes

  • There is no AC input.
  • AC power supply is out of phase.
  • The voltage regulator starts over/low voltage protection.
  • The voltage regulator fails.

Procedure

  1. Check whether there are any correlated alarm

    Check whether ALM-2362 No Mains Supply Alarm is reported on the alarm system. Handle ALM-2362 No Mains Supply Alarm according to the corresponding handling suggestions. Check whether the alarm is cleared.

    Y=> The alarm handling ends.

    N=> Go to Step 2.

    If no such alarms are reported, go the Step [2].

  2. Measure the input voltage of the voltage regulator

    Measure the input AC voltage of the voltage regulator to see whether it is between 150V and 300V.

    Y=> Go to Step 4.

    N=>Go to Step 3.

  3. Check the AC mains supply

    Check whether the AC mains supply is in normal operation (the output voltage should be between 150V and 300V). Clear the faults of the mains supply if any. View whether the alarm is cleared.

    Y=>The alarm handling ends.

    N=>Contact Huawei Customer Service Center

  4. Set Bypass switch to ON position

    Set the Bypass switch (on the panel of the voltage regulator) to ON position. View whether the BTS works normally.

    Y=>The alarm may be caused by faults of the voltage regulator. Please contact Huawei Customer Service Center to replace the voltage regulator.

    N=>Set the Bypass switch back to OFF position.Please contact Huawei Customer Service Center for solutions.