ALM-3834 Over Temperature Alarm

Description

This alarm is reported when the equipment room temperature exceeds the upper limit.

Attribute

Alarm ID Alarm Severity Alarm Type
3834 Critical Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

13:EAC

3 Board No.

Number of the fault board

0:EAC0

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

9: BTS3002C

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The DRU over temperature protection may be caused and the services are interrupted.

System Actions

None.

Possible Causes

  • The environment temperature is higher than the set upper limit.
  • The upper limit is not properly set.
  • The temperature sensor or its connecting cable is faulty.
  • The main board of the environment box is faulty.

Procedure

  1. Check the upper limit of the environment box to see if it is properly set.

    Y=>Go to Step 3.

    N=>Go to Step 2.

  2. Re-set a reasonable upper limit and see if the alarm is cleared.

    Y=>The alarm is cleared. Alarm handling is completed.

    N=>Go to Step 3.

  3. Check if the equipment room temperature is too high.

    The normal working temperature range of the BTS30 and the BTS312 is -5oC - 45oC. Check if the equipment room temperature is higher than the set upper limit.

    Y=>Go to Step 4.

    N=>Go to Step 5.

  4. Turn on the air conditioner to lower the temperature.

    Y=>The alarm is cleared. Alarm handling is completed.

    N=>The alarm is not cleared. Go to Step 5.

  5. Check the temperature sensor and its connecting cable and see if the connection is OK.

    Y=>Go to Step 7.

    N=>Go to Step 6.

  6. Connecting the temperature sensor cable and see if the alarm is cleared.

    Y=>The alarm is cleared. Alarm handling is completed.

    N=>The alarm is not cleared. Go to Step 7.

  7. Replace the temperature sensor and its connecting cable and see if the alarm is cleared.

    Y=>The alarm is cleared. Alarm handling is completed.

    N=>Go to Step 8.

  8. Replace the main board of the alarm box and see if the alarm is cleared.

    Y=>The alarm is cleared. Alarm handling is completed.

    N=>The alarm is not cleared.Please contact Huawei Customer Service Center