ALM-4942 Access Control Alarm

Description

This alarm is reported when the cabinet door is open or not properly closed.

Attribute

Alarm ID Alarm Severity Alarm Type
4942 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

64:DOMU

3 Board No.

Number of the fault board

0-7:DOMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255: None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

13:BTS3006C;

14:BTS3002E;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

None

System Actions

None

Possible Causes

  • The cabinet door is open.
  • The access control sensor is faulty.
  • The cable that connects the access control sensor is faulty.

Procedure

  1. Check whether the cabinet door is open.

    Y=> Check whether the equipment inside the cabinet is damaged. If yes, repair the damaged equipment. The alarm handling is complete.

    N=> Go to Step 2.

  2. Check the access control sensor and the cable that connects the access control sensor.

    Replace the damaged access control sensor or the cable that connects the access control sensor and check whether the alarm is cleared.

    Y=> The alarm handling is complete.

    N=>The alarm is not cleared. Please contact Huawei Customer Service Center.


Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.