ALM-5640 Ambient Humidity Too Low

Description

This alarm is reported when the ambient humidity is lower than the lower humidity threshold. The default lower humidity threshold is 10%.

Attribute

Alarm ID Alarm Severity Alarm Type
5640 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

72:DPMU

133:APM/APMU

3 Board No.

Number of the fault board

Value range:0-8:DPMU/APMU/APM

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255: None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

12:BTS3012;

13:BTS3006C;

14:BTS3002E;

15:BTS3012AE;

16:BTS3012 II;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The BTS hardware may be damaged if this alarm occurs.

System Actions

None.

Possible Causes

  • The ambient humidity is too low.
  • The setting of lower humidity threshold is not reasonable.
  • The humidity sensor fails. The cables that connect the humidity sensor are faulty.
  • The PMU of the power system is faulty.

Procedure

  1. Check the threshold of the ambient humidity alarm.
    1. View the threshold of the humidity alarm, and check whether the lower humidity threshold is correct:

      Y => The setting is correct. Go to procedure 2.

      N => The setting is wrong. Go to step b.

    2. Change the threshold of the ambient humidity alarm.
    3. Check whether the alarm is cleared:

      Y => The alarm is cleared. The alarm handling ends.

      N => The alarm is not cleared. Go to procedure 2.

  2. Check the air conditioner or heat exchanger.
    1. Check whether the air conditioner or heat exchanger is functional:

      Y => The air conditioner or heat exchanger is functional. Go to procedure 3.

      N => The air conditioner or heat exchanger is faulty. Go to step b.

    2. Repair the air conditioner or heat exchanger.
    3. Check whether the alarm is cleared:

      Y => The alarm is cleared. The alarm handling ends.

      N => The alarm is not cleared. Go to procedure 3.

  3. Replace the temperature and humidity sensor.
    1. Replace the temperature and humidity sensor.
    2. Check whether the alarm is cleared:

      Y => The alarm is cleared. The alarm handling ends.

      N => The alarm is not cleared. Contact Huawei Customer Service Center.