ALM-5700 No AC Input Alarm

Description

This alarm is reported when there is no mains supply.

Attribute

Alarm ID Alarm Severity Alarm Type
5700 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

72:DPMU

133:APM/APMU

3 Board No.

Number of the fault board

Value range:0-8:DPMU/APMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255: None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

12:BTS3012;

13:BTS3006C;

14:BTS3002E;

15:BTS3012AE;

16:BTS3012 II;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

20:DBS3036;

21:BTS3036;

22:BTS3036A;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The service capacity of the BTS is reduced, or the BTS is out of service.

System Actions

When this alarm is generated, the BSC blocks the non-BCCH TRXs of the BTS to reduce the power consumption and to maximize the service time of the BTS.

Possible Causes

The single-phase AC mains supply is input to the PMU. The PMU internal power monitoring module monitors the AC voltage. This alarm will be generated when the voltage is lower than 50 V.

Procedure

  1. At the site, check whether the AC power supply is abnormal.

    Y => The AC power supply is abnormal. Contact the power supply department to rectify the power failure. After the AC power supply is normal, go to [2].

    N => The AC power supply is normal. Go to 3.

  2. Check whether the alarm is cleared.

    Y => The alarm is cleared. The alarm handling is complete.

    N => The alarm is not cleared. Go to 3.

  3. Check whether the power switch of the cabinet or equipment room is set to OFF.

    Y => The power switch of the cabinet or equipment room is set to OFF. Go to 4.

    N => The power switches of the cabinet and equipment room are all set to ON. Go to 5.

  4. Set the power switches of the cabinet and equipment room to ON. Check whether the alarm is cleared.

    Y => The alarm is cleared. The alarm handling is complete.

    N => The alarm is not cleared. Go to 5.

  5. Check whether the connections of power cables in the equipment room are faulty.

    Y => The connections of power cables in the equipment room are faulty. Contact the power supply department to rectify the fault. Then, go to [6].

    N => The connections of power cables in the equipment room are normal. Contact Huawei Customer Service Center.

  6. Check whether the alarm is cleared.

    Y => The alarm is cleared. The alarm handling is complete.

    N => The alarm is not cleared. Contact Huawei Customer Service Center.