ALM-5734 AC Lightning Arrester Failure Alarm

Description

This alarm is reported when the AC lightning arrester is abnormal.

Attribute

Alarm ID Alarm Severity Alarm Type
5734 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

133:APM/APMU

3 Board No.

Number of the fault board

Value range:0-8:APMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255: None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

13:BTS3006C;

14:BTS3002E;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The lightning arrester is damaged, and thus the BTS may be damaged by lightning.

System Actions

None.

Possible Causes

  • The No AC Input Alarm, AC Undervoltage Alarm, or Lack Of Phase Alarm is generated.
  • The alarm level is set incorrectly.
  • The alarm signaling cable of the surge protector is damaged or improperly installed.
  • The AC surge protector is faulty.

Procedure

  1. If the No AC Input Alarm, AC Undervoltage Alarm, or Lack Of Phase Alarm is generated, clear these alarm before clearing the AC Surge Protector Fault Alarm.

  2. Replace the alarm signaling cable of the AC surge protector. Check whether the alarm is cleared:

    Y => The alarm is cleared. No further action is required.

    N => The alarm is not cleared. Go to step 3.

  3. Check the alarm voltage, if the third alarm voltage of the APMU is not set to low level. Set the alarm voltage to low level. Check whether the alarm is cleared:

    Y => The alarm is cleared. No further action is required.

    N => The alarm is not cleared. Go to step 4.

  4. Replace the PDU of the AC surge protector. Check whether the alarm is cleared:

    Y => The alarm is cleared. No further action is required.

    N => The alarm is not cleared. Contact Huawei Customer Service Center.