ID | Name | Meaning |
---|---|---|
1 | Site No. | Number of the site where the faulty board or module is located Value range: 0-2047 |
2 | Board Type | Number of the type which the faulty board belongs to. 72:DPMU |
3 | Board No. | Number of the fault board Value range:0-8:DPMU |
4 | PassNo | Number of the passage where the faulty board is located. |
5 | SubLink No. | Alarm sub-category number 255: None |
6 | Cell Index | Index of the cell where the board or module is located 0-2047: Cell index of the faulty cell in the data configuration 65535: None |
7 | Site Type | Type of the site where the faulty board is located. 3:BTS30; 5:BTS312; 10:BTS3012A; 11:BTS3006A; 12:BTS3012; 13:BTS3006C; 14:BTS3002E; 15:BTS3012AE; 16:BTS3012 II; 17:DBS3900 GSM; 18:BTS3900 GSM; 19:BTS3900A GSM; |
8 | RackNo | Number of the rack where the faulty board is located. |
9 | BoxNo | Number of the subrack where the faulty board is located. |
10 | SlotNo | Number of the slot where the faulty board is located. |
11 | Site Name | Site Name |
12 | Alarm Attribute | Alarm Character 0:Normal 1:Transient Count |
The services may be interrupted due to low environment temperature of the boards.
Check the Upper Temperature Thrsh. and Lower Temperature Thrsh. , and then check whether the temperature is lower than the threshold.
Y=> Go to Step 2.
N=> The temperature is normal. Go to Step 3.
Check the air conditioner and the fan. Clear the faults if any. View whether the alarm is cleared after the internal temperature of the cabinet resumes normal.
Y=> The alarm handling ends.
N=> Go to Step 3.
Check the temperature sensor. Replace the temperature sensor if faulty. View whether the alarm is cleared.
Y=> The alarm handling ends.