ID | Name | Meaning |
---|---|---|
1 | Site No. | Number of the site where the faulty board or module is located Value range: 0-2047 |
2 | Board Type | Number of the type which the faulty board belongs to. 72:DPMU |
3 | Board No. | Number of the fault board Value range:0-8:DPMU |
4 | PassNo | Number of the passage where the faulty board is located. |
5 | SubLink No. | Alarm sub-category number 255: None |
6 | Cell Index | Index of the cell where the board or module is located 0-2047: Cell index of the faulty cell in the data configuration 65535: None |
7 | Site Type | Type of the site where the faulty board is located. 3:BTS30; 5:BTS312; 10:BTS3012A; 11:BTS3006A; 12:BTS3012; 13:BTS3006C; 14:BTS3002E; 15:BTS3012AE; 16:BTS3012 II; 17:DBS3900 GSM; 18:BTS3900 GSM; 19:BTS3900A GSM; |
8 | RackNo | Number of the rack where the faulty board is located. |
9 | BoxNo | Number of the subrack where the faulty board is located. |
10 | SlotNo | Number of the slot where the faulty board is located. |
11 | Site Name | Site Name |
12 | Alarm Attribute | Alarm Character 0:Normal 1:Transient Count |
Run the LST BTSEXD command on the MML client.
The higher humidity threshold can be viewed.
Y=>Go to step 2.
N=>The humidity is normal, go to step [3].
Lower the humidity by air conditioner and see if the alarm is cleared.
Y=>The alarm is cleared. Alarm handling is completed.
N=>The alarm is not cleared. Go to Step4.
Check whether the upper humidity threshold is set higher than normal. Note that the normal humidity for the BTS is from15%RH to 85%RH.
Y=>Modify the upper humidity threshold and check if the alarm is cleared. The alarm is cleared. Alarm handling is completed. The alarm is not cleared. Go to Step 4.
The operation procedure is as follows:
Run the SET BTSEXD command on the MML client.
Set the upper humidity threshold to 85%RH.
N=> Go to step 4.
See if the alarm is cleared.
Y=>The alarm is cleared. Alarm handling is completed.
N=>The alarm is not cleared. Please contact Huawei Customer Service Center.