ID | Name | Meaning |
---|---|---|
1 | Site No. | Number of the site where the faulty board or module is located Value range: 0-2047 |
2 | Board Type | Number of the type which the faulty board belongs to. 72:DPMU |
3 | Board No. | Number of the fault board Value range:0-8:DPMU |
4 | PassNo | Number of the passage where the faulty board is located. |
5 | SubLink No. | Alarm sub-category number 255: None |
6 | Cell Index | Index of the cell where the board or module is located 0-2047: Cell index of the faulty cell in the data configuration 65535: None |
7 | Site Type | Type of the site where the faulty board is located. 3:BTS30; 5:BTS312; 10:BTS3012A; 11:BTS3006A; 12:BTS3012; 13:BTS3006C; 14:BTS3002E; 15:BTS3012AE; 16:BTS3012 II; 17:DBS3900 GSM; 18:BTS3900 GSM; 19:BTS3900A GSM; |
8 | RackNo | Number of the rack where the faulty board is located. |
9 | BoxNo | Number of the subrack where the faulty board is located. |
10 | SlotNo | Number of the slot where the faulty board is located. |
11 | Site Name | Site Name |
12 | Alarm Attribute | Alarm Character 0:Normal 1:Transient Count |
The smog may be caused by fire. Services may be interrupted if the fire spreads over the cabinet.
Check whether the equipment room catches fire.
Y=> Put out the fire if any. Reset the smog sensor. Check if the Alarm is cleared. The alarm is cleared. Alarm handling is completed. The alarm is not cleared. Go to Step 2.
N=> Go to Step 2.
Reset the smog sensor and then replace it. View whether the alarm is cleared. (The later operation is unnecessary if the alarm is cleared upon the completion of the reset).
Y=> The alarm handling ends.