ALM-5872 Rack Infrared Alarm

Description

This alarm is triggered when the cabinet door is open.

Attribute

Alarm ID Alarm Severity Alarm Type
5872 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

72:DPMU

3 Board No.

Number of the fault board

Value range:0-8:DPMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255: None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

3:BTS30;

5:BTS312;

10:BTS3012A;

11:BTS3006A;

12:BTS3012;

13:BTS3006C;

14:BTS3002E;

15:BTS3012AE;

16:BTS3012 II;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

None.

System Actions

None.

Possible Causes

  • The cabinet door is open.
  • The infrared sensor or the cable connecting to the infrared sensor is damaged.

Procedure

  1. Check whether the cabinet is open

    Y=> Check whether the equipment room and the devices are damaged. Repair them if any damaged. The alarm handling ends if the alarm is cleared after the repair.

    N=> Go to Step 2.

  2. Check the infrared sensor and the connection cable

    Replace the infrared sensor or the connection cable if faulty. View whether the alarm is cleared.

    Y=> The alarm handling ends.

    N=> Please contact Huawei Customer Service Center.