ALM-5992 AC Over Voltage Alarm

Description

This alarm is reported when the mains supply voltage is above the upper limit( default value :280V).

Attribute

Alarm ID Alarm Severity Alarm Type
5992 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

72:DPMU

3 Board No.

Number of the fault board

Value range:0-8:DPMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255: None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

12:BTS3012;

13:BTS3006C;

14:BTS3002E;

15:BTS3012AE;

16:BTS3012 II;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

None.

System Actions

None.

Possible Causes

The PMU monitors the AC voltage. This alarm will be generated when the voltage is higher than the threshold (default value :280V).

Procedure

  1. Check whether the PSU is faulty.

  2. Check the threshold of the AC overvoltage alarm.
    1. Check the AC voltage.
    2. Check the threshold of the AC overvoltage alarm.
    3. Check whether the AC voltage exceeds the threshold:

      Y => The AC power supply network and the cable connection in the equipment room are faulty. Perform onsite checks, and contact the power supply departments and property departments to troubleshoot the faults on the power supply network. If the input AC power is normal but the alarm persists, Contact Huawei Customer Service Center.

      N => If the current voltage of the AC power is basically within the operating range and the alarm is cleared automatically, you can infer that the power supply is instable. For example, the power supply is interrupted, or overvoltage or undervoltage occurs. Otherwise, contact Huawei Customer Service Center.


Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.