ALM-6016 Battery Temperature Too Low Alarm

Description

This alarm is reported when the battery temperature is too low.

Attribute

Alarm ID Alarm Severity Alarm Type
6016 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

72:DPMU

3 Board No.

Number of the fault board

Value range:0-8:DPMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255: None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

12:BTS3012;

13:BTS3006C;

14:BTS3002E;

15:BTS3012AE;

16:BTS3012 II;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

None.

System Actions

None.

Possible Causes

This alarm is generated when the power system detects that the battery temperature is below the set lower limit.

Procedure

  1. Check the battery temperature alarm threshold.
    1. Check if the battery temperature alarm threshold is set properly.

      Y=>Go to Step 2.

      N=>Go to Step b.

    2. Modify the battery temperature alarm threshold and see if the alarm is cleared.

      Y=>The alarm is cleared. Alarm handling is completed.

      N=>The alarm is not cleared. Go to Step 2.

  2. Check the heat exchanger.
    1. Check if the heat exchanger works normally.

      Y=>Go to Step 3.

      N=>Go to Step b.

    2. Check and mend the heat exchanger if necessary. Ensure that it works normally. See if the alarm is cleared.

      Y=>The alarm is cleared. Alarm handling is completed.

      N=>The alarm is not cleared. Go to Step 3.

  3. Replace the temperature sensor and see if the alarm is cleared.

    Y=>The alarm is cleared. Alarm handling is completed.

    N=>The alarm is not cleared. Please contact Huawei Customer Service Center.


Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.