ALM-6416 Over Humidity Alarm

Description

This alarm is reported when the humidity of the environment is higher than the threshold (default: 80%).

Attribute

Alarm ID Alarm Severity Alarm Type
6416 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

70:DEMU/EMU

3 Board No.

Number of the fault board

0-2:DEMU/EMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

12:BTS3012;

13:BTS3006C;

14:BTS3002E;

15:BTS3012AE;

16:BTS3012 II;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The BTS hardware may be destroyed if the alarm is reported.

System Actions

None.

Possible Causes

  • The environment humidity is higher than the upper humidity threshold.
  • The setting of the upper humidity threshold is improper.
  • The humidity sensor is faulty.
  • The cable connecting to the humidity sensor is faulty.
  • The lightening protection board is faulty.
  • The environment monitoring module is faulty.

Procedure

  1. Judge the causes according to other alarm information.

    None.

  2. Find out other causes.
    1. Check if the humidity upper threshold of the DEMU is properly set.

      Run the DSP BTSENVSTAT command on the MML client.

      Check whether the Humidity high limit is set reasonably.

      Y=> Go to Step c.

      N=> Go to Step b.

    2. Reset the upper humidity threshold. Check if the alarm is cleared.

      Y=> The alarm is cleared.

      N=> The alarm is not cleared. Go to Step c.

    3. Check whether the humidity sensor works normally.

      Y=> The alarm is cleared.

      N=> The alarm is not cleared. Go to Step d.

    4. Make sure that the cable of the humidity sensor is properly connected.

      Y=> The alarm is cleared.

      N=> The alarm is not cleared. Go to Step e.

    5. Check whether the lightning protection board works normally.

      Y=> The alarm is cleared.

      N=> The alarm is not cleared. Go to Step f.

    6. Reset the environment monitoring module by software or hardware. Check if the alarm is cleared.

      Y=> The alarm is cleared.

      N=> The alarm is not cleared. Please contact Huawei Customer Service Center.