ALM-6510 Door Open Alarm

Description

The alarm is reported when the door of the machine room or cabinet is open, triggering the door status sensor.

Attribute

Alarm ID Alarm Severity Alarm Type
6510 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

70:DEMU/EMU

3 Board No.

Number of the fault board

0-2:DEMU/EMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

12:BTS3012;

13:BTS3006C;

14:BTS3002E;

15:BTS3012AE;

16:BTS3012 II;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

This alarm indicates that the equipment may be intruded.

System Actions

None.

Possible Causes

  • The door of the machine room or cabinet is open.
  • The door status sensor or the cables connecting it are faulty.
  • The switches are set incorrectly.
  • The DEMU is faulty.

Procedure

  1. Check the status of the door of the equipment room.
    1. Check whether the maintenance engineer opens the door:

      Y=> Go to procedure 5.

      N=> Go to step b.

    2. Check on site whether someone enters the equipment room illegally:

      Y=> Somebody illegally opens the door of the equipment room. Go to step c.

      N=> Nobody illegally opens the door of the equipment door. Go to procedure 2.

    3. .
  2. Check the alarm level of the door status alarm.
    1. Check the alarm level of the door status alarm. The door status alarm is triggered in high level.

      Y => The setting is correct. Go to procedure 3.

      N => Reset the alarm level of the door status alarm. Go to step b.

    2. .
    3. Check whether the alarm is cleared:

      Y => The alarm is cleared. The alarm handling ends.

      N => The alarm is not cleared. Go to procedure 3.

  3. Replace the door status sensor.
    1. Replace the door status sensor.
    2. .
    3. Check whether the alarm is cleared:

      Y => The alarm is cleared. The alarm handling ends.

      N => The alarm is not cleared. Go to procedure 4.

  4. Replace the EMU.
    1. Replace the EMU manually.
    2. Check whether the alarm is cleared:

      Y => The alarm is cleared. The alarm handling ends.

      N => The alarm is not cleared. Contact Huawei Customer Service Center.

  5. Clear the alarm on the RNC side.