ALM-9732 Fan Subassembly Communication Alarm

Description

This alarm is reported when communication between the fan monitoring board inside the fan box and the DTMU interrupts for more than 240 seconds.

Attribute

Alarm ID Alarm Severity Alarm Type
9732 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

69:NFCB

93:FMU

94:FMUA

3 Board No.

Number of the fault board

0-5:NFCB/FMU/FMUA

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

255:None

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

12:BTS3012;

13:BTS3006C;

14:BTS3002E;

15:BTS3012AE;

16:BTS3012 II;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

  • The fan box cannot communicate with the DTMU or report the alarm or adjust the speed through the main control unit. The fan is auto set to full speed after the alarm.
  • The alarm severity is critical.

System Actions

None.

Possible Causes

  • Improper installation (probably).
  • The MON0 port of the UPEU board is faulty.

Procedure

  1. Check the cable connection between the FMUA board and the BBU and between the COM IN port on the FMUA and the MON0 port on the UPEU.
    1. If the cable is not securely connected, connect the cable properly. Then, check whether the alarm is cleared.

      Y => The alarm is cleared. End the alarm handling.

      N => The alarm is not cleared. Go to step 2.

    2. .
  2. Check the software configuration of the FMUA board. If the alarm is not cleared. Go to step [3].

  3. Replace the FMUA board. Check whether the alarm is cleared:

    Y => The alarm is cleared. No further action is required.

    N => The alarm is not cleared. Contact Huawei Customer Service Center.