The BSC power cables are classified into external power cables and internal power cables. The power cables are mandatory, which consist of -48 V power cables and RTN power cables.
The BSC external power cables need to be installed on site. They are used to lead the power from the power distribution frame (PDF) to the power distribution box in the BSC. The BSC internal power cables are installed before delivery. They are used to lead the power from the power distribution box to each board and module in the BSC.
Table 1 lists the BSC external power cables.
Name |
Color |
Cross-Sectional Area (Unit: mm2) |
Connector Type/Installation Position (Power Distribution Box) |
Connector Type/Installation Position (PDF) |
Quantity |
---|---|---|---|---|---|
External -48 V power cable |
Blue |
25/35 |
Cord end terminal/-48 V input of the BSC6000 cabinet |
OT terminal/-48 V output of the PDF |
2 per cabinet |
External RTN power cable |
Black |
25/35 |
Cord end terminal/-48 V input of the BSC6000 cabinet |
OT terminal/-48 V output of the PDF |
2 per cabinet |
Table 2 lists the BSC internal power cables.
Name |
Color |
Cross-Sectional Area (Unit: mm2) |
Connector Type/Installation Position (Power Distribution Box) |
Connector Type/Installation Position (Subrack) |
Quantity |
---|---|---|---|---|---|
Internal -48 V power cable |
Blue |
8 |
Cord end terminal/-48 V input terminal |
OT terminal/-48 V output terminal |
2 per subrack |
Internal RTN power cable |
Black |
8 |
Cord end terminal/-48 V input terminal |
OT terminal/-48 V output terminal |
2 per subrack |
The BSC external power cable and the BSC internal power cable have the same appearance, as shown in Figure 1.
Name |
Color |
Cross-Sectional Area (Unit: mm2) |
Connector Type/Installation Position (Power Distribution Box) |
Connector Type/Installation Position (PDF) |
Quantity |
---|---|---|---|---|---|
External -48 V power cable |
Blue |
25/35 |
OT terminal/-48 V input of the BSC6000 cabinet |
OT terminal/-48 V output of the PDF |
2 per cabinet |
External RTN power cable |
Black |
25/35 |
OT terminal/-48 V input of the BSC6000 cabinet |
OT terminal/-48 V output of the PDF |
2 per cabinet |
Name |
Color |
Cross-Sectional Area (Unit: mm2) |
Connector Type/Installation Position (Power Distribution Box) |
Connector Type/Installation Position (Subrack) |
Quantity |
---|---|---|---|---|---|
Internal -48 V power cable |
Blue |
8 |
OT terminal/-48 V input terminal |
OT terminal/-48 V output terminal |
2 per subrack |
Internal RTN power cable |
Black |
8 |
OT terminal/-48 V input terminal |
OT terminal/-48 V output terminal |
2 per subrack |
Figure 2 shows the BSC external power cable or the BSC internal power cable.