Customized Alarm Ports of the DBS3900/BTS3900/BTS3900A Base Station

This describes the mapping between internal alarm IDs of the BTS and environment alarm ports and cables of each monitoring device. The monitoring devices are the EMUA, UPEU, UEIU, APMI, and FMUA.

Environment Alarm Ports of the EMUA

On the LMT, the EMUA is displayed as "DEMU". The EMUA is connected to the MON1 port of the UPEU or the UEIU through the RS485 signal cable.

Table 1 describes the relation between the alarm IDs and the environment alarm ports/cables of the EMUA.
NOTE:

Alarm ID in all the tables of this section is the BTS internal alarm ID. The BSC alarm ID should be planned separately.

Table 1 Mapping between alarm IDs and environment alarm ports/cables of the EMUA

Site Type

Monitoring Unit Port

Subrack No./Slot No.

Port No.

Alarm ID

Monitoring Cable and BOM

Wire

Wire Color

BTS3900 GSM,

BTS3900A GSM,

DBS3900 GSM

S1+/S1-

Slot 0 or slot 1 of subrack 2

1

6292

Self-contained cables of the sensor

Not involved

Not involved

S2+/S2-

2

6294

S3+/S3-

3

6296

S4+/S4-

4

6298

S5+/S5-

5

6300

S6+/S6-

6

6302

S7+/S7-

7

6304

S8+/S8-

8

6306

S9+/S9-

9

6308

S10+/S10-

10

6310

S11+/S11-

11

6312

S12+/S12-

12

6314

S13+/S13-

13

6316

S14+/S14-

14

6318

S15+/S15-

15

6320

S16+/S16-

16

6322

S17+/S17-

17

6324

S18+/S18-

18

6326

S19+/S19-

19

6328

S20+/S20-

20

6330

S21+/S21-

21

6332

S22+/S22-

22

6334

S23+/S23-

23

6336

S24+/S24-

24

6338

S25+/S25-

25

6340

S26+/S26-

26

6342

S27+/S27-

27

6344

S28+/S28-

28

6346

S29+/S29-

29

6348

S30+/S30-

30

6350

S31+/S31-

31

6352

S32+/S32-

32

6354

Environment Alarm Ports of the UPEU

The Boolean alarms related to the UPEU are reported through the GTMU. Therefore, you should set " Subrack No." and "Slot No." of the GTMU by running the command "SET ALMPORT".

Table 2 describes the mapping between alarm IDs and environment alarm ports/cables of the UPEU.

Table 2 Mapping between alarm IDs and environment alarm ports/cables of the UPEU

Site Type

Monitoring Unit Port

Subrack No./Slot No.

Port No.

Alarm ID

Monitoring Cable and BOM

Wire

Wire Color

Description

BTS3900 GSM,

BTS3900A GSM,

DBS3900 GSM

EXT-ALM0

The UPEU is configured in slot 19 of subrack 0.

The GTMU is configured in slot 6 of subrack 0.

9

5048

BBU Boolean alarm cable

X1.1/X1.2

Orange-white/orange

Boolean input 1+/Boolean input 1- (GND)

10

5050

X1.3/X1.6

Green-white/green

Boolean input 2+/Boolean input 2- (GND)

11

5052

X1.5/X1.4

Blue-white/blue

Boolean input 3+/Boolean input 3- (GND)

12

5054

X1.7/X1.8

Brown-white/brown

Boolean input 4+/Boolean input 4- (GND)

EXT-ALM1

13

5056

X1.1/X1.2

Orange-white/orange

Boolean input 5+/Boolean input 5- (GND)

14

5058

X1.3/X1.6

Green-white/Green

Boolean input 6+/Boolean input 6- (GND)

15

5060

X1.5/X1.4

Blue-white/blue

Boolean input 7+/Boolean input 7- (GND)

16

5062

X1.7/X1.8

Brown-white/brown

Boolean input 8+/Boolean input 8- (GND)

NOTE:
  • Each Boolean value is represented by one bit.
  • The UPEU can also be configured in slot 18 of subrack 0. The corresponding port number ranges from 1 to 8. The alarm 5048 is mapped with port 1 and the alarm 5050 is mapped with port 2. The mapping between the alarm ID and the port number can be deduced by analogy.

Environment Alarm Ports of the UEIU

The Boolean alarms related to the UEIU are reported through the GTMU. Therefore, you should set " Subrack No." and "Slot No." of the GTMU by running the command "SET ALMPORT".

Table 3 describes the mapping between alarm IDs and environment alarm ports/cables of the UEIU.

Table 3 Relation between alarm IDs and environment alarm ports/cables of the UEIU

Site Type

Monitoring Unit Port

Subrack No./Slot No.

Port No.

Alarm ID

Monitoring Cable and BOM

Wire

Wire Color

Description

BTS3900 GSM,

BTS3900A GSM,

DBS3900 GSM

EXT-ALM0

The UEIU is configured in slot 18 of subrack 0.

The GTMU is configured in slot 6 of subrack 0.

1

5032

BBU Boolean alarm cable

X1.1/X1.2

Orange-white/orange

Boolean input 9+/Boolean input 9- (GND)

2

5034

X1.3/X1.6

Green-white/green

Boolean input 10+/Boolean input 10- (GND)

3

5036

X1.5/X1.4

Blue-white/blue

Boolean input 11+/Boolean input 11- (GND)

4

5038

X1.7/X1.8

Brown-white/brown

Boolean input 12+/Boolean input 12- (GND)

EXT-ALM1

5

5040

X1.1/X1.2

Orange-white/orange

Boolean input 13+/Boolean input 13- (GND)

6

5042

X1.3/X1.6

Green-white/green

Boolean input 14+/Boolean input 14- (GND)

7

5044

X1.5/X1.4

Blue-white/blue

Boolean input 15+/Boolean input 15- (GND)

8

5046

X1.7/X1.8

Brown-white/brown

Boolean input 16+/Boolean input 16- (GND)

NOTE:

The UEIU can also be configured in slot 19 of subrack 0. The corresponding port number ranges from 9 to 16. The alarm 5032 is mapped with port 9 and the alarm 5034 is mapped with port 10. The mapping between the alarm ID and the port number can be deduced by analogy.

Environment Alarm Ports of the APMI

On the LMT, the APMI is displayed as APMU.

Table 4 describes the mapping between alarm IDs and environment alarm ports/cables of the APMI.

Table 4 Mapping between alarm IDs and environment alarm ports/cables of the APMI

Site Type

Monitoring Unit Port

Subrack No./Slot No.

Port No.

Alarm ID

Monitoring Cable and BOM

Wire

Wire Color

BTS3900 GSM,

BTS3900A GSM,

DBS3900 GSM

IN1

Slot 2 or slot 3 of subrack 2

1

5758

Self-contained cables of the sensor

Not involved

Not involved

IN2

2

5760

IN3

3

5762

Environment Alarm Ports of the FMUA

On the LMT, the FMUA is displayed as FMU.

Table 5 describes the relation between the alarm IDs and the environment alarm ports/cables of the FMUA.

Table 5 Mapping between alarm IDs and environment alarm ports/cables of the FMUA

Site Type

Monitoring Unit Port

Subrack No./Slot No.

Port No.

Alarm ID

Monitoring Cable and BOM

Wire

Wire Color

BTS3900A GSM

SW0

Slot 8 to slot 11 of subrack 2

0

9760

Self-contained cables of the sensor

Not involved

Not involved

SW1

1

9762

Self-contained cables of the sensor

Not involved

Not involved

SW2

2

9764

Self-contained cables of the sensor

Not involved

Not involved

SW3

3

9766

Self-contained cables of the sensor

Not involved

Not involved


Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.