1. The BSC must communicate properly with the BTS.
2. The BTS is configured with the battery equipment.
ID | Name | Description |
---|---|---|
IDXTYPE | Index Type | Meaning: how to specify a BTS Value range: BYNAME(By Name), BYIDX(By Index) Explanation: This parameter determines whether to specify a BTS by its name or index. Default value: None |
STIDX | Site Index | Meaning: BTS index Value range: 0-2047 Explanation: 1. This parameter specifies the number of a BTS. Each BTS is numbered uniquely in a BSC. 2. This parameter is mandatory if Index Type is set to BYIDX(By Index). Default value: None |
STNAME | Site Name | Meaning: BTS name Value range: 1-32 characters Explanation: 1. This parameter specifies the name of the target BTS. Each BTS is named uniquely in a BSC. 2. This parameter is mandatory if Index Type is set to BYNAME(By Name). Default value: None |
SRN | Subrack No. | Meaning: subrack number Value range: 0-53 Explanation: This parameter specifies the number of the subrack in which the BTS power module is located. The subrack number is unique in a BTS. Default value: None |
SN | Slot No. | Meaning: slot number Value range: 0-23 Explanation: This parameter specifies the number of the slot that holds the BTS power module. Default value: None |
Query the battery test result (Index Type = BYIDX(By Index); Site Index = 0; Subrack No. = 0; Slot No. = 15): DSP BTSBATTTST: IDXTYPE=BYIDX, BTSIDX=0, SRN=0, SN=15; The result is as follows: +++ HUAWEI 2008-01-12 17:05:29 O&M #1320 %% DSP BTSBATTTST: IDXTYPE=BYIDX, BTSIDX=0, SRN=0, SN=15;%% RETCODE = 0 Execution succeeded Test No. 1 Test Type Simple test Starting Time of the Test 2008-01-12 17:05 Test Result Successful Battery Efficiency 50 Discharging Interval 15 Final Voltage of Discharging 20 Average Discharging Current 2.5 Total AH of Discharge 23 Power Cabinet Temperature 35 Test End Reason Ended manually --- END
Domain Name | Description |
---|---|
Test No. | Test number |
Test Type | Value range: Manual Test, Automatic test after AC input failure, Timed automatic test, Simplified test, Without test |
Starting Time of the Test | Start time of the test |
Test Result | Value range: Without result, Battery operation normal, Battery operation caution in advance, Battery alarm |
Battery Efficiency | Battery efficiency |
Discharging Interval | Discharging interval |
Final Voltage of Discharging | Final voltage of discharging |
Average Discharging Current | Average discharging current |
Total AH of Discharge | Total AH of discharging |
Power Cabinet Temperature | Power cabinet temperature |
Test End Reason | Value range: Battery voltage lower than the set final voltage, Exceed test duration, Automatic test after AC input failure stop due to AC input recovery, Manual stop, Stop due to failure alarm |