Modify BSC EAC(MOD EAC)

Function

A configuration command that modifies the parameters of the environment monitoring device. In this command, Subrack No. uniquely identifies the EAC.

Note

1. If the attributes of the environment monitoring device support floating-point input, the input precision must be two significant digits.

2. If the attributes of the environment monitoring device support floating-point input, the value range is -32768.00 to 32767.00.

Parameters

ID Name Description
SRN Subrack No.

Meaning:Subrack No.

Value range:0~11

Explanation:This parameter specifies the number of the subrack where the environment monitoring instrument is located.

Default value:None

POWER_RELAY1 Switch for Relay 1

Meaning:Switch for Relay 1

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies the state of the relay. The relay has two states: Open and Close. Open indicates that the relay coil is powered on. Close indicates that the relay coil is powered off.

Default value:None

POWER_RELAY2 Switch for Relay 2

Meaning:Switch for Relay 2

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies the state of the relay. The relay has two states: Open and Close. Open indicates that the relay coil is powered on. Close indicates that the relay coil is powered off.

Default value:None

POWER_RELAY3 Switch for Relay 3

Meaning:Switch for Relay 3

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies the state of the relay. The relay has two states: Open and Close. Open indicates that the relay coil is powered on. Close indicates that the relay coil is powered off.

Default value:None

POWER_RELAY4 Switch for Relay 4

Meaning:Switch for Relay 4

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies the state of the relay. The relay has two states: Open and Close. Open indicates that the relay coil is powered on. Close indicates that the relay coil is powered off.

Default value:None

POWER_RELAY5 Switch for Relay 5

Meaning:Switch for Relay 5

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies the state of the relay. The relay has two states: Open and Close. Open indicates that the relay coil is powered on. Close indicates that the relay coil is powered off.

Default value:None

POWER_RELAY6 Switch for Relay 6

Meaning:Switch for Relay 6

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies the state of the relay. The relay has two states: Open and Close. Open indicates that the relay coil is powered on. Close indicates that the relay coil is powered off.

Default value:None

EX_ANO1_SIG_MAX Upper Limit of Signal Output of External Analog 1

Meaning:Upper Limit of Signal Output of External Analog 1

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of signal output of external analog 1. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the accuracy of the measured value may be influenced. It is recommended that you retain the default value.

Default value:None

EX_ANO1_SIG_MIN Lower Limit of Signal Output of External Analog 1

Meaning:Lower Limit of Signal Output of External Analog 1

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of signal output of external analog 1. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the accuracy of the measured value may be influenced. It is recommended that you retain the default value.

Default value:None

EX_ANO1_VAL_MAX Upper Limit of Measurement Range of External Analog 1

Meaning:Upper Limit of Measurement Range of External Analog 1

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of measurement range for external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the measurement range of the sensor may not be correct. It is recommended that you retain the default value.

Default value:None

EX_ANO1_VAL_MIN Lower Limit of Measurement Range of External Analog 1

Meaning:Lower Limit of Measurement Range of External Analog 1

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of measurement range of the external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the measurement range of the sensor may not be correct. It is recommended that you retain the default value.

Default value:None

EX_ANO2_SIG_MAX Upper Limit of Signal Output of External Analog 2

Meaning:Upper Limit of Signal Output of External Analog 2

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of the signal output of external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the accuracy of the measured value may be influenced. It is recommended that you retain the default value.

Default value:None

EX_ANO2_SIG_MIN Lower Limit of Signal Output of External Analog 2

Meaning:Lower Limit of Signal Output of External Analog 2

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of the signal output of external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the accuracy of the measured value may be influenced. It is recommended that you retain the default value.

Default value:None

EX_ANO2_VAL_MAX Upper Limit of Measurement Range of External Analog 2

Meaning:Upper Limit of Measurement Range of External Analog 2

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of measurement range for external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the measurement range of the sensor may not be correct. It is recommended that you retain the default value.

Default value:None

EX_ANO2_VAL_MIN Lower Limit of Measurement Range of External Analog 2

Meaning:Lower Limit of Measurement Range of External Analog 2

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of measurement range of the external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the measurement range of the sensor may not be correct. It is recommended that you retain the default value.

Default value:None

EX_ANO3_SIG_MAX Upper Limit of Signal Output of External Analog 3

Meaning:Upper Limit of Signal Output of External Analog 3

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of the signal output of external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the accuracy of the measured value may be influenced. It is recommended that you retain the default value.

Default value:None

EX_ANO3_SIG_MIN Lower Limit of Signal Output of External Analog 3

Meaning:Lower Limit of Signal Output of External Analog 3

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of the signal output of external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the accuracy of the measured value may be influenced. It is recommended that you retain the default value.

Default value:None

EX_ANO3_VAL_MAX Upper Limit of Measurement Range of External Analog 3

Meaning:Upper Limit of Measurement Range of External Analog 3

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of measurement range for external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the measurement range of the sensor may not be correct. It is recommended that you retain the default value.

Default value:None

EX_ANO3_VAL_MIN Lower Limit of Measurement Range of External Analog 3

Meaning:Lower Limit of Measurement Range of External Analog 3

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of measurement range for external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the measurement range of the sensor may not be correct. It is recommended that you retain the default value.

Default value:None

EX_ANO4_SIG_MAX Upper Limit of Signal Output of External Analog 4

Meaning:Upper Limit of Signal Output of External Analog 4

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of the signal output of external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the accuracy of the measured value may be influenced. It is recommended that you retain the default value.

Default value:None

EX_ANO4_SIG_MIN Lower Limit of Signal Output of External Analog 4

Meaning:Lower Limit of Signal Output of External Analog 4

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of the signal output of external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the accuracy of the measured value may be influenced.

It is recommended that you retain the default value.

Default value:None

EX_ANO4_VAL_MAX Upper Limit of Measurement Range of External Analog 4

Meaning:Upper Limit of Measurement Range of External Analog 4

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of measurement range for external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the measurement range of the sensor may not be correct. It is recommended that you retain the default value.

Default value:None

EX_ANO4_VAL_MIN Lower Limit of Measurement Range of External Analog 4

Meaning:Lower Limit of Measurement Range of External Analog 4

Value range:1-8 characters

Explanation:This parameter indicates the lower limit of measurement range for external analog sensor. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, the measurement range of the sensor may not be correct. It is recommended that you retain the default value.

Default value:None

VOL48_MASK Enable Voltage Alarm Reporting for 48 V Power Supply

Meaning:Enable Voltage Alarm Reporting for 48 V Power Supply

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report a -48 V power supply alarm. When this parameter is set to Open, an alarm is reported if the -48 V power supply is not normal.

Default value:None

VOL24_MASK Enable Voltage Alarm Reporting for 24 V Power Supply

Meaning:Enable Voltage Alarm Reporting for 24 V Power Supply

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report a 24 V power supply alarm. When this parameter is set to Open, an alarm is reported if the 24 V power supply is not normal.

Default value:None

TEMP_MASK Enable Temperature Alarm Reporting

Meaning:Enable Temperature Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report a temperature alarm. When this parameter is set to Open, a temperature alarm is reported if the temperature exceeds the threshold.

Default value:None

HUM_MASK Enable Humidity Alarm Reporting

Meaning:Enable Humidity Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report a humidity alarm. When this parameter is set to Open, a humidity alarm is reported if the humidity exceeds the threshold.

Default value:None

EX_ANO1_MASK Enable Analog Parameter 1 Alarm Reporting

Meaning:Enable Analog Parameter 1 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external analog alarm. When this parameter is set to Open, an alarm is reported if the external analog signal output or the measurement range exceeds the threshold.

Default value:None

EX_ANO2_MASK Enable Analog Parameter 2 Alarm Reporting

Meaning:Enable Analog Parameter 2 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external analog alarm. When this parameter is set to Open, an alarm is reported if the external analog signal output or the measurement range exceeds the threshold.

Default value:None

EX_ANO3_MASK Enable Analog Parameter 3 Alarm Reporting

Meaning:Enable Analog Parameter 3 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external analog alarm. When this parameter is set to Open, an alarm is reported if the external analog signal output or the measurement range exceeds the threshold.

Default value:None

EX_ANO4_MASK Enable Analog Parameter 4 Alarm Reporting

Meaning:Enable Analog Parameter 4 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external analog alarm. When this parameter is set to Open, an alarm is reported if the external analog signal output or the measurement range exceeds the threshold.

Default value:None

WATER_MASK Enable Water Alarm Reporting

Meaning:Enable Water Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report a water damage alarm. When this parameter is set to Open, a water damage alarm is reported if the water sensor detects abnormal signals.

Default value:None

SMOKE_MASK Enable Smoke Alarm Reporting

Meaning:Enable Smoke Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report a smoke alarm. When this parameter is set to Open, a smoke alarm is reported if the smoke sensor detects abnormal signals.

Default value:None

INFRA_RED_MASK Enable Infrared Sensor Alarm Reporting

Meaning:Enable Infrared Sensor Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an infrared alarm. When this parameter is set to Open, an alarm is reported if the infrared sensor detects abnormal signals.

Default value:None

DOOR_ENGINE_MASK Enable Door Status Alarm Reporting

Meaning:Enable Door Status Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report a door status alarm. When this parameter is set to Open, a door status alarm is reported if the door status sensor detects abnormal signals.

Default value:None

EX_SWITCH1_MASK Enable External Switch 1 Alarm Reporting

Meaning:Enable External Switch 1 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH2_MASK Enable External Switch 2 Alarm Reporting

Meaning:Enable External Switch 2 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH3_MASK Enable External Switch 3 Alarm Reporting

Meaning:Enable External Switch 3 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH4_MASK Enable External Switch 4 Alarm Reporting

Meaning:Enable External Switch 4 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH5_MASK Enable External Switch 5 Alarm Reporting

Meaning:Enable External Switch 5 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH6_MASK Enable External Switch 6 Alarm Reporting

Meaning:Enable External Switch 6 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH7_MASK Enable External Switch 7 Alarm Reporting

Meaning:Enable External Switch 7 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH8_MASK Enable External Switch 8 Alarm Reporting

Meaning:Enable External Switch 8 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH9_MASK Enable External Switch 9 Alarm Reporting

Meaning:Enable External Switch 9 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH10_MASK Enable External Switch 10 Alarm Reporting

Meaning:Enable External Switch 10 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH11_MASK Enable External Switch 11 Alarm Reporting

Meaning:Enable External Switch 11 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH12_MASK Enable External Switch 12 Alarm Reporting

Meaning:Enable External Switch 12 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH13_MASK Enable External Switch 13 Alarm Reporting

Meaning:Enable External Switch 13 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH14_MASK Enable External Switch 14 Alarm Reporting

Meaning:Enable External Switch 14 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH15_MASK Enable External Switch 15 Alarm Reporting

Meaning:Enable External Switch 15 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH16_MASK Enable External Switch 16 Alarm Reporting

Meaning:Enable External Switch 16 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH17_MASK Enable External Switch 17 Alarm Reporting

Meaning:Enable External Switch 17 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH18_MASK Enable External Switch 18 Alarm Reporting

Meaning:Enable External Switch 18 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH19_MASK Enable External Switch 19 Alarm Reporting

Meaning:Enable External Switch 19 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH20_MASK Enable External Switch 20 Alarm Reporting

Meaning:Enable External Switch 20 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH21_MASK Enable External Switch 21 Alarm Reporting

Meaning:Enable External Switch 21 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH22_MASK Enable External Switch 22 Alarm Reporting

Meaning:Enable External Switch 22 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH23_MASK Enable External Switch 23 Alarm Reporting

Meaning:Enable External Switch 23 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH24_MASK Enable External Switch 24 Alarm Reporting

Meaning:Enable External Switch 24 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH25_MASK Enable External Switch 25 Alarm Reporting

Meaning:Enable External Switch 25 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH26_MASK Enable External Switch 26 Alarm Reporting

Meaning:Enable External Switch 26 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH27_MASK Enable External Switch 27 Alarm Reporting

Meaning:Enable External Switch 27 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH28_MASK Enable External Switch 28 Alarm Reporting

Meaning:Enable External Switch 28 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH29_MASK Enable External Switch 29 Alarm Reporting

Meaning:Enable External Switch 29 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH30_MASK Enable External Switch 30 Alarm Reporting

Meaning:Enable External Switch 30 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH31_MASK Enable External Switch 31 Alarm Reporting

Meaning:Enable External Switch 31 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

EX_SWITCH32_MASK Enable External Switch 32 Alarm Reporting

Meaning:Enable External Switch 32 Alarm Reporting

Value range:CLOSE(Close),OPEN(Open)

Explanation:This parameter specifies whether to report an external switch alarm. When this parameter is set to Open, an external switch alarm is reported if the external switch sensor detects abnormal signals.

Default value:None

VOL48_THD_HIGH Upper Limit of Voltage Alarm for 48 V Power Supply

Meaning:Upper Limit of Voltage Alarm for 48 V Power Supply

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of voltage alarm for 48 V power supply. If the voltage of the 48 V power supply is higher than this parameter, the Abnormal Voltage alarm is generated.

Default value:None

VOL48_THD_LOW Lower Limit of Voltage Alarm for 48 V Power Supply

Meaning:Lower Limit of Voltage Alarm for 48 V Power Supply

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of voltage alarm for 48 V power supply. If the voltage of the 48 V power supply is lower than this parameter, the Abnormal Voltage alarm is generated.

Default value:None

VOL24_THD_HIGH Upper Limit of Voltage Alarm for 24 V Power Supply

Meaning:Upper Limit of Voltage Alarm for 24 V Power Supply

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of voltage alarm for 24 V power supply. If the voltage of the 24 V power supply is higher than this parameter, the Abnormal Voltage alarm is generated.

Default value:None

VOL24_THD_LOW Lower Limit of Voltage Alarm for 24 V Power Supply

Meaning:Lower Limit of Voltage Alarm for 24 V Power Supply

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of voltage alarm for 24 V power supply. If the voltage of the 24 V power supply is lower than this parameter, the Abnormal Voltage alarm is generated.

Default value:None

TEMP_THD_HIGH Upper Limit of Temperature Alarm

Meaning:Upper Limit of Temperature Alarm

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of the temperature alarm.

If the temperature of the cabinet where the environment monitor device is located is higher than this parameter, the Abnormal Temperature alarm is generated.

Default value:None

TEMP_THD_LOW Lower Limit of Temperature Alarm

Meaning:Lower Limit of Temperature Alarm

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of the temperature alarm.

If the temperature of the cabinet where the environment monitor device is located is lower than this parameter, the Abnormal Temperature alarm is generated.

Default value:None

HUM_THD_HIGH Upper Limit of Humidity Alarm

Meaning:Upper Limit of Humidity Alarm

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of the humidity alarm. If the ambient humidity of the environment monitor device is higher than this parameter, the Abnormal Humidity alarm is generated.

Default value:None

HUM_THD_LOW Lower Limit of Humidity Alarm

Meaning:Lower Limit of Humidity Alarm

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of the humidity alarm. If the ambient humidity of the environment monitor device is lower than this parameter, the Abnormal Humidity alarm is generated.

Default value:None

EX_ANO1_THD_HIGH Upper Limit of Analog Parameter 1

Meaning:Upper Limit of Analog Parameter 1

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of external analog alarm. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, some alarms may not be reported. It is recommended that you retain the default value.

Default value:None

EX_ANO1_THD_LOW Lower Limit of Analog Parameter 1

Meaning:Lower Limit of Analog Parameter 1

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of external analog alarm. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, some alarms may not be reported. It is recommended that you retain the default value.

Default value:None

EX_ANO2_THD_HIGH Upper Limit of Analog Parameter 2

Meaning:Upper Limit of Analog Parameter 2

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of external analog alarm. If the value of the analog is higher than the parameter, a related alarm is reported. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, some alarms may not be reported. It is recommended that you retain the default value.

Default value:None

EX_ANO2_THD_LOW Lower Limit of Analog Parameter 2

Meaning:Lower Limit of Analog Parameter 2

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of external analog alarm. If the value of the analog is lower than the parameter, a related alarm is reported. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, some alarms may not be reported. It is recommended that you retain the default value.

Default value:None

EX_ANO3_THD_HIGH Upper Limit of Analog Parameter 3

Meaning:Upper Limit of Analog Parameter 3

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of external analog alarm. If the value of the analog is higher than the parameter, a related alarm is reported. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, some alarms may not be reported. It is recommended that you retain the default value.

Default value:None

EX_ANO3_THD_LOW Lower Limit of Analog Parameter 3

Meaning:Lower Limit of Analog Parameter 3

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of external analog alarm. If the value of the analog is lower than the parameter, a related alarm is reported. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, some alarms may not be reported. It is recommended that you retain the default value.

Default value:None

EX_ANO4_THD_HIGH Upper Limit of Analog Parameter 4

Meaning:Upper Limit of Analog Parameter 4

Value range:1-9 characters

Explanation:This parameter indicates the upper limit of external analog alarm. If the value of the analog is higher than the parameter, a related alarm is reported. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, some alarms may not be reported. It is recommended that you retain the default value.

Default value:None

EX_ANO4_THD_LOW Lower Limit of Analog Parameter 4

Meaning:Lower Limit of Analog Parameter 4

Value range:1-9 characters

Explanation:This parameter indicates the lower limit of external analog alarm. If the value of the analog is lower than the parameter, a related alarm is reported. The parameter is a floating-point value set by the user according to the actual situation.

If the parameter is set to an overgreat or oversmall value, some alarms may not be reported. It is recommended that you retain the default value.

Default value:None

Example

1. Modify the parameters of the BSC environment monitoring device (Subrack No. = 0; Switch for Relay 1 = OPEN(Open)):
MOD EAC: SRN=0, POWER_RELAY1=OPEN;
2. Modify the parameters of the BSC environment monitoring device (Enable Voltage Alarm Reporting for 24 V Power Supply = OPEN(Open)):
MOD EAC: VOL24_MASK=OPEN;
Related reference
Add BSC EAC(ADD EAC)