Parameter Name |
Upper Limit of Voltage Alarm for 48 V Power Supply(V) |
---|---|
Description |
This parameter indicates the upper limit of voltage alarm for 48 V power supply. If the voltage of the 48 V power supply is higher than this parameter, the Abnormal Voltage alarm is generated. |
GUI Value Range |
[42.00,57.00] |
Default Value |
57.00 |
Unit |
Volts |
Step |
- |
Modification Rules |
None |
Configuration Policy |
If this parameter is set to an overlarge or oversmall value, some alarms may not be reported. Huawei recommends that you retain the default value. |
Recommended Value |
57.00 |
Parameter Relationship |
None |
BSC Feature |
None |
Parameter Class |
Parameters About Equipment |
Caution |
If the environment monitor device uses the 24 V power supply, the alarms related to the 48 V power supply are not reported. Upper Limit of Voltage Alarm for 48V Power Supply cannot be smaller than Lower Limit of Voltage Alarm for 48V Power Supply. |