Load Power-off Voltage(V)

Parameter Name

Load Power-off Voltage(V)

Description

When the battery voltage of any power supply unit in a BTS is lower than the value of this parameter, the hierarchical power-off function is enabled. All the BTS cabinets enable the level-2 power-off function and switch off the power amplifiers of all the TRXs. After all the batteries reach the normal voltage, the BTS can work properly.

GUI Value Range

[35.1,55.3]

Default Value

44.0

Unit

Volts

Step

-

Modification Rules

None

Configuration Policy

None

Recommended Value

44.0

Parameter Relationship

None

BSC Feature

None

Parameter Class

Parameters About Equipment

Caution

None


Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.