Parameter Name |
Even Charging Voltage (V) |
---|---|
Description |
The value of this parameter must be greater than the Float Charging Voltage and smaller than the DC Overvoltage Alarm Threshold minus 1. After the Even Charging Voltage and Float Charging Voltage are set, the batteries are charged on the basis of the two voltage values. |
GUI Value Range |
[43.3,57.6] |
Default Value |
56.5 |
Unit |
Volts |
Step |
- |
Modification Rules |
None |
Configuration Policy |
None |
Recommended Value |
56.5 |
Parameter Relationship |
None |
BSC Feature |
None |
Parameter Class |
Parameters About Equipment |
Caution |
None |