Parameter Name |
Charge Coefficient |
---|---|
Description |
This parameter specifies the charge coefficient used to limit the maximum charging current when a battery is charged. The maximum charging current can be set to the capacity of the battery cabinet multiplied by 0.05 to 0.25. That is, the charge coefficient ranges from 0.05 to 0.25. By default, it is set to 0.15 to prolong the life cycle of the battery and to maximize the charge effect. For example, if the capacity of a battery cabinet is 200 Ah and the charge coefficient is 0.15, then the maximum charging current is 30 A. |
GUI Value Range |
[0.05C,0.07C,0.10C,0.12C,0.15C,0.18C,0.20C,0.22C,0.25C] |
Default Value |
0.15C |
Unit |
None |
Step |
- |
Modification Rules |
None |
Configuration Policy |
None |
Recommended Value |
0.15C |
Parameter Relationship |
None |
BSC Feature |
None |
Parameter Class |
Parameters About Equipment |
Caution |
None |