ALM-4746 Air-conditioner/heat-exchanger alarm

Description

The alarm is triggered when the air conditioner or heat exchanger is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type
4746 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

64:DTMU/DOMU

87:GTMU

3 Board No.

Number of the fault board

0-5:DTMU/GTMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

0:air conditioner

1:heat exchanger

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

3:BTS30;

5:BTS312;

10:BTS3012A;

11:BTS3006A;

12:BTS3012;

13:BTS3006C;

14:BTS3002E;

15:BTS3012AE;

16:BTS3012 II;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

The ambient temperature of the BTS may become abnormal, and the normal operation of the BTS is affected.

System Actions

None

Possible Causes

  • Power failure (BTS configured with batteries)
  • Faulty connections between the air conditioner or heat exchanger and the backplane
  • Faulty air conditioner or heat exchanger

Procedure

  1. Check for related alarms.
    1. Run the LST ALMAF command on the MML client. Check whether ALM-5988 No Mains Supply Alarm is reported on the LMT.

      Y => The alarm is reported on the LMT. Go to step b.

      N => ALM-5988 No Mains Supply Alarm is not reported on the LMT. Go to 2.

    2. Rectify the fault according to handling suggestions in ALM-5988 No Mains Supply Alarm. Check whether the alarm is cleared.

      Y => The alarm is cleared. The alarm handling is complete.

      N => The alarm is not cleared. Go to 2.

  2. Check the cable connections.
    1. Check whether the cable is faulty.

      Y => The cable is faulty. Go to step b.

      N => The cable is normal. Go to 3.

    2. Replace the cable between the air conditioner or heat exchanger and the backplane. Check whether the alarm is cleared.

      Y => The alarm is cleared. The alarm handling is complete.

      N => The alarm is not cleared. Go to 3.

  3. Check the air conditioner or heat exchanger.
    1. Check the air conditioner or heat exchanger for faults.

      Y => The air conditioner or heat exchanger is faulty. Go to step b.

      N => The air conditioner and the heat exchanger are normal. Contact Huawei Customer Service Center.

    2. Replace the air conditioner or heat exchanger. Check whether the alarm is cleared.

      Y => The alarm is cleared. The alarm handling is complete.

      N => The alarm is not cleared. Contact Huawei Customer Service Center.