ID | Name | Meaning |
---|---|---|
1 | Site No. | Number of the site where the faulty board or module is located Value range: 0-2047 |
2 | Board Type | Number of the type which the faulty board belongs to. 64:DTMU/DOMU 87:GTMU |
3 | Board No. | Number of the fault board 0-5:DTMU/GTMU |
4 | PassNo | Number of the passage where the faulty board is located. |
5 | SubLink No. | Alarm sub-category number 0:air conditioner 1:heat exchanger |
6 | Cell Index | Index of the cell where the board or module is located 0-2047: Cell index of the faulty cell in the data configuration 65535: None |
7 | Site Type | Type of the site where the faulty board is located. 3:BTS30; 5:BTS312; 10:BTS3012A; 11:BTS3006A; 12:BTS3012; 13:BTS3006C; 14:BTS3002E; 15:BTS3012AE; 16:BTS3012 II; 17:DBS3900 GSM; 18:BTS3900 GSM; 19:BTS3900A GSM; |
8 | RackNo | Number of the rack where the faulty board is located. |
9 | BoxNo | Number of the subrack where the faulty board is located. |
10 | SlotNo | Number of the slot where the faulty board is located. |
11 | Site Name | Site Name |
12 | Alarm Attribute | Alarm Character 0:Normal 1:Transient Count |
The ambient temperature of the BTS may become abnormal, and the normal operation of the BTS is affected.
Y => The alarm is reported on the LMT. Go to step b.
N => ALM-5988 No Mains Supply Alarm is not reported on the LMT. Go to 2.
Y => The alarm is cleared. The alarm handling is complete.
N => The alarm is not cleared. Go to 2.
Y => The cable is faulty. Go to step b.
N => The cable is normal. Go to 3.
Y => The alarm is cleared. The alarm handling is complete.
N => The alarm is not cleared. Go to 3.
Y => The air conditioner or heat exchanger is faulty. Go to step b.
N => The air conditioner and the heat exchanger are normal. Contact Huawei Customer Service Center.
Y => The alarm is cleared. The alarm handling is complete.
N => The alarm is not cleared. Contact Huawei Customer Service Center.