ALM-5682 PSU Illegal Alarm

Description

This alarm is reported when no PSU is configured but physically a PSU is inserted.

Attribute

Alarm ID Alarm Severity Alarm Type
5682 Major Fault

Parameters

ID Name Meaning
1 Site No.

Number of the site where the faulty board or module is located

Value range: 0-2047

2 Board Type

Number of the type which the faulty board belongs to.

72:DPMU

133:APM/APMU

3 Board No.

Number of the fault board

Value range:0-8:DPMU/APM/APMU

4 PassNo

Number of the passage where the faulty board is located.

5 SubLink No.

Alarm sub-category number

0: PSU0 Illegal alarm

1: PSU1 Illegal alarm

2: PSU2 Illegal alarm

3: PSU3 Illegal alarm

4: PSU4 Illegal alarm

5: PSU5 Illegal alarm

6: PSU6 Illegal alarm

7: PSU7 Illegal alarm

8: PSU8 Illegal alarm

9: PSU9 Illegal alarm

6 Cell Index

Index of the cell where the board or module is located

0-2047: Cell index of the faulty cell in the data configuration

65535: None

7 Site Type

Type of the site where the faulty board is located.

12:BTS3012;

13:BTS3006C;

14:BTS3002E;

15:BTS3012AE;

16:BTS3012 II;

17:DBS3900 GSM;

18:BTS3900 GSM;

19:BTS3900A GSM;

8 RackNo

Number of the rack where the faulty board is located.

9 BoxNo

Number of the subrack where the faulty board is located.

10 SlotNo

Number of the slot where the faulty board is located.

11 Site Name

Site Name

12 Alarm Attribute

Alarm Character

0:Normal

1:Transient Count

Impact on the System

None.

System Actions

None.

Possible Causes

The configuration data does not contain PSU data while a PSU is physically inserted.

Procedure

  1. Check the configuration for the PSU in the power system. Check whether the number of PSUs and the slot numbers for the PSU in the configuration data are consistent with the number of actually inserted PSUs and the slot numbers.

    Y=> Go to step 3.

    N=> Go to step 2.

  2. Remove the inserted PSU and check whether the alarm is cleared.

    Y=> The alarm is cleared. The alarm handling is complete.

    N=> The alarm is not cleared. Go to step 3.

  3. Replace the PMU that monitors the power supply system, and then check whether the alarm is cleared.

    Y=>The alarm is cleared. Alarm handling is complete.

    N=> The alarm is not cleared. Please contact Huawei Customer Service Center.